The air shower room is a kind of local purification equipment with strong generality, which is used to remove dust on the surface of people or objects when people or goods enter the clean area Common troubleshooting of the air shower room: 1 Power switch Generally, there are four places in the air shower room where the power can be cut off: 1 Power switch of the air shower outdoor box; 2 Control panel of the air shower indoor box 3 On the external boxes on both sides of the air shower room (the power switch here can prevent the power supply from being cut off in case of emergency and effectively improve the personal safety of the staff) When the power indicator is not working, it is not necessary to recheck the power supply of the above four air shower rooms II The fan in the air shower doesn't work: when the air shower doesn't work, * time to check whether the emergency switch of the box outside the air shower is cut off If it is cut off, press it gently with your hand and turn it to the right to release it
III fan reversing or wind speed in the air shower room is very small: please check whether the 380V three-phase four wire line is reversed Generally, the air shower room manufacturer will have a specially assigned electrician to connect the line when the factory is installed; if the wire source in the air shower room is reversed, the light one will cause the fan in the air shower room not to work or the reverse one will reduce the wind speed in the air shower room, and the heavy one will burn the circuit board of the whole air shower room; It is suggested that enterprises using the air shower room should not change the wiring lightly If it is determined to move due to production needs, please consult the air shower room manufacturer for solutions IV no spraying in the air shower room: in addition to the above three points, it is also necessary to check whether the emergency stop key inside the air shower room box is pressed If the emergency stop key is warp color, the air shower room will not be sprayed; if the emergency stop key is pressed again, it can work normally V the air shower can not automatically sense the shower: please check the light sensing system in the lower right corner of the air shower box to see whether the light sensing device is installed correctly If the two sides of the light sensing are facing each other and the light sensing is normal, the air shower can automatically sense the shower Vi the wind speed in the air shower room is very low for a period of time: please check whether there is too much dust on the primary filter and filter in the air shower room If so, please replace the filter (the primary filter in the air shower shall be replaced once in 1-6 months, and the filter in the air shower shall be replaced once in 6-12 months).