PE or XLPE cables above 1.
8/3 (3.
6) kV and EPR or PVC cables above 3.
6/6 (7.
2) kV must be partially
discharged.
For multicore cables, a voltage must be applied between each conductor and the metal shield, and all cores should be tested
.
b.
The partial discharge test is carried out according to the provisions of IEC-540, and the partial discharge test sensitivity is ≤ 20pC for EPR, PE and XLPE cables, 40pC for PVC cable≤s, and 10pC
for EPR and XL≤PE cables of 21/35, 26/35kV.
At 1.
5'U_0', EPR, PE and XLPE cables do not exceed 20pC, PVC cables do not exceed 40pC, and EPR and XLPE cables of 21/35, 26/35kV do not exceed 10pC
.
a.
PE or XLPE cables above 1.
8/3 (3.
6) kV and EPR or PVC cables above 3.
6/6 (7.
2) kV must be partially
discharged.
For multicore cables, a voltage must be applied between each conductor and the metal shield, and all cores should be tested
.
b.
The partial discharge test is carried out according to the provisions of IEC-540, and the partial discharge test sensitivity is ≤ 20pC for EPR, PE and XLPE cables, 40pC for PVC cable≤s, and 10pC
for EPR and XL≤PE cables of 21/35, 26/35kV.
At 1.
5'U_0', EPR, PE and XLPE cables do not exceed 20pC, PVC cables do not exceed 40pC, and EPR and XLPE cables of 21/35, 26/35kV do not exceed 10pC
.